320 kW Open Type Natural Gas Generator
320 kW open type natural gas generator: 400 kVA, 280 kW continuous. For food, cold storage and factories past 250 kW; turnkey install by Aden Solar.
- Rated power
- 320 kW
- Apparent power
- 400 kVA
- Continuous power
- 280 kW
- Generating efficiency
- 36.5%
- Step load acceptance
- ±150 kW
- Frequency
- 50 / 60 Hz
- Voltage
- 0.4 / 0.6 / 10.5 kV
- Weight
- 3,000 kg
- Dimensions (L×W×H)
- 2900×1400×2000 mm
The 320 kW Open Type Natural Gas Generator is a generator set delivering 400 kVA apparent power and 280 kW continuous power, with 36.5% generating efficiency at full load. It is designed for installation in an existing generator room at sites that have outgrown the 250 kW class but do not need 500 kW, such as food processing plants, cold stores and plastics or metal workshops. At 2900×1400×2000 mm and 3,000 kg it fits a standard engine room.
Key features
- 400 kVA apparent power, 280 kW continuous power
- 36.5% generating efficiency at full load
- ±150 kW step load acceptance, sized for compressor and pump starts
- 50 / 60 Hz; 0.4 kV low voltage plus 0.6 kV and 10.5 kV medium voltage output
- Runs on natural gas, with no diesel storage, refuelling or stock tracking
Where it is used
- Cold stores with refrigeration compressors running around the clock
- Food processing, dairy and bakery plants
- Workshops with injection moulding, CNC and welding lines
- Shopping and business centres with a plant room
What does the generator room need?
- Enough fresh air intake for combustion and cooling, and a hot air outlet
- A safe exhaust route out of the building
- A level foundation that carries the set, with clearance around it for maintenance
- A natural gas line of sufficient capacity, with meter and regulator
Installation with Aden Solar
Aden Solar reviews your current consumption and peak loads during the site survey to confirm whether the 320 kW class is the right fit. We deliver a turnkey installation covering gas and exhaust design, transfer panel, mounting, commissioning and maintenance, and can run the generator in the same system as a solar plant.
Frequently asked questions
If 250 kW is not enough, should I choose 320 kW or 500 kW?
If your continuous load is above 225 kW and stays around 280 kW, the 320 kW set fits. If the site draws close to 450 kW continuously or plans to grow soon, look at the 500 kW class.
What does step load acceptance mean?
It is how much load the generator can pick up in a single step. At ±150 kW for this set, it determines how stable voltage and frequency stay when a large compressor or pump starts suddenly.
Is a 320 kW generator 400 kVA?
Yes. 400 kVA apparent power equals 320 kW of active power at a 0.8 power factor, and the set is sized to deliver 280 kW in continuous operation.